Mermaid Datalogger
![]() |
Product name: | MERMAID DATALOGGER | ||||
| Item number: | MLMMD | |||||
| Description : | This datalogger monitors, records and help troubleshoot multiple motors at the same time. Perfect for wastewater lift stations. | |||||
Overview
The Mermaid electrical datalogger is a very small AC and battery powered datalogger able to monitor 3 phases for 3 motors plus 4 digital inputs and one analog input. It reads every input 10 times per second. A reading is recorded only when its value has changed. This way, for most lift stations, it is possible to record near one month of data before the newest rools over the oldest. Each motor input can be used to record frequency and current or voltage.
This device is perfect for preventive maintenance and troubleshooting electrical equipment. It could tell which motor, pump or equipment will probably fail next. It can find intermittent problems in minutes instead of hours or days, without replacing parts! Do not stop production if you do not have to.
Small, this datalogger can be hidden in the electrical panel and work several weeks on 2 C batteries.
Benefits
- Easy installation – Stations stays in operation during installation
- Ensures, without the need for on-site calibration, high levels of accuracy in any flow condition
- Automatically corrects the effects of temperature on level measurement.
- Easy installation with fast setup and no calibration required.
- Cellular Wireless and other communication formats available
- Economical, compact solution for flow monitoring
- A higher level of accuracy
- Easy installation, no profiling required
- Incredible Storage capacity
- Dynamic logging intervals ensures data is collected as conditions change
- Optional rainfall logging feature records and characterizes rain events.
- Disconnectable sensor for quick and easy field replacement
- Less Maintenance and Troubleshooting
- On-site sensor operation verification prior to leaving the site.
- Quick installation with no calibration required.
- Rain gauge connection, optional
Ideal Applications
- Information Program
- Billing / Custody Transfer
- Capacity Studies
- Collection Systems
- Combined Sewer Overflows (CSO) Studies and Monitoring
- Inflow and Infiltration (I&I) Studies
- Short Term and Long-Term Flow Monitoring
- NPDES Stormwater Compliance
- Permanent Collection System Monitoring
- Plant Influent and Effluent
- Sanitary Sewer Evaluation Studies
Specifications
6.75in./17.2cm
3in./8cm |
6.75in./17.2cm
3in./8cm |
6.75in./17.2cm
2.5in./6.5cm |
2.5in./6.5cm
3in./8cm |
Need Mermaid Software to use recorded data |
| Front | Bottom | Top | Side |
Specifications |
|
| Name/Item No. | Mermaid Datalogger / MLMMD |
| Product type | Multiple motor electrical recorder |
| Types of data recorded (always time stamped) | Based on sensor selection, but usually frequency, current, voltage, rain, analog and digital inputs, etc. |
| Number of digital inputs | 4, with reserved for rain |
| Reading speed of digital input | 10 Hz |
| Analog inputs | 1 software set to 4-20mA or 0-5V, 9 electrical |
| Type of electrical inputs | 9 inputs for current, voltage or analog modules (4-20mA, 0-5V, 0-10V, 0-24V) |
| Analog input reading speed | 10 Hz |
| Analog input accuracy | ± 0.1 %. This do not include the sensor precision |
| Digital output | 1, activated with alarm setup or remote manually. |
| Internal temperature sensor accuracy | ± 3°C |
| Memory | 2 Mb |
| Memory (number of records) | 500,000 |
| External power | 3 VDC 1 Amp |
| Operation time on batteries | 2 weeks |
| Type of batteries | 2 types C alcalines batteries or rechargeables |
| Integrated battery charger | YES |
| Download | RS232, USB using a cable converter, Land line modem, cellular modem, Ethernet using Serial converter |
| Communication Interface | RS232 (DB9) |
| Installation Options | DIN Rail |
| Dimension (inches) | 3 x 2.5 x 6.75 |
| Dimensions (cm) | 8 x 6.5 x 17.2 |
| Weight including 2 type C batteries | 1 lb/0.45 kg |
| Warranty | 3 years, parts and labor |
Accessories and Options
| Part No | Description |
| Software | |
| MLSOFTM | Mermaid software |
| Power supply | |
| MLPS1 | 90-240V AC 3 VDC 2 A |
| Connectors (for current sensors) | |
| MLCTA6 | Connector for 3 MLCT150 or MLCT300 |
| Current sensors | |
| MLCT5-15-75 | Mini current sensor with selector 5A, 15A and 75A |
| MLCT150 | Current Clamps 150 Amps |
| MLCT300 | Current Clamps 300 Amps |
| MLCTP1500 | Precision current sensors 1500Amps |
| Voltage sensor and accessories | |
| MLPT600 | 3 phases 680 Volts voltage transformer |
| MLPTCBLY | Wires and clamps for Wye configuration |
| MLPTCBLD | Wires and clamps for Delta configuration |
| Analog input converters (to use on motor inputs) | |
| MLAI420A | 4-20mA analog input converter |
| MLAI05V | 0-5V analog input converter |
| MLAI010V | 0-10V analog input converter |
| MLAI024V | 0-24V analog input converter |
| Digital input converter | |
| MLLI120 | Live Interface 12-120V (convert voltage status to ON/OFF for digital inputs) |
| Communication | |
| MLUSB232 | USB to RS-232 serial adaptor |
| MLCB232MF6 | RS-232 extension cable 6′ |
| MLERS232 | Ethernet-Serial RS232 Interface |
| MCELETH | Cellular Modem with Ethernet port |
| Other Accessories | |
| MLRG1 | Rain gauge NWS approved |
| MLCASE1 | Aluminum briefcase with moulded separators |
| MLPL | Wastewater pressure sensor for level and force main |
Video and Download
See how easy it is to install the Mermaid datalogger |
Send us an email to receive a notification regarding the availability of new downloads for this product. |
Specifications can change without notice.